Term Function Technical data Description
17 RELAY-1 (HORN RELAY)
Output 10A/28VDC This relay has programmable function,
selectable from a list.
18 RELAY-2 (STOP RELAY)
Output 10A/28VDC This relay has programmable function,
selectable from a list.
19 START RELAY
Output 10A/28VDC This relay controls the engine cranking.
20 FUEL RELAY
Output 10A/28VDC This relay is used for fuel solenoid control. It is
internally connected to terminal 16 for
supplying the charge alternator’s excitation
current.
21 EMERGENCY STOP
22 SPARE-2
23 PROGRAM LOCK
24 SPARE-1
25 COOLANT LEVEL
26 HIGH TEMP
27 LOW OIL PRESSURE
28 RECTIFIER FAIL
Digital inputs These inputs have programmable
characteristics selected via the program
menu. Each input may be driven by a
normally closed or ‘normally open contact,
switching either battery+ or battery-. The
effect of the switch is also selectable from a
list. See PROGRAMMING section for more
details.
29 CURR_W+
30 CURR_W-
31 CURR_V+
32 CURR_V-
33 CURR_U+
34 CURR_U-
Current transformer
inputs, 5A-AC
Connect the generator current transformer
terminals to these inputs. Do not connect the
same current transformer to other instruments
otherwise a unit fault will occur. Connect each
terminal of the transformer to the unit’s related
terminal. Do not use common terminals. Do
not use grounding. Correct polarity of
connection is vital. If the measured power is
negative, then change the polarity of each 3
current transformers. The rating of the
transformers should be the same for each of
the 3 phases. The secondary winding rating
shall be 5 Amperes. (For ex. 200/5 Amps).