DKG-307 User Manual V-01.03
(14.02.2006)
- 14 -
7. WEEKLY OPERATION SCHEDULE
In most applications, the genset is requested to operate only in working hours. Thanks to the
weekly program feature unwanted operation of the genset may be prohibited.
The unit has one programmable turn-on/turn-off time pairs for each day of week. These
programmable parameters allow the genset to operate automatically only in allowed time limits.
The weekly operation schedule is only active in AUTO mode. In other modes it will not affect the
genset operation.
In AUTO mode, if the operation of the genset is disabled by the weekly schedule, then the AUTO
led will flash (instead of a steady on state).
Each turn-on/turn-off time is defined in 10 minute steps. These parameters are defined in the
parameters P_051 to P_064. On the display, the parameters are shown with 3 digits, the first 2 digit are the
hour and the last digit is the first digit of the minutes. For example 19.3 will mean 19:30.
Unused programs should be set to 24.0.
An example setup may be as follows:
P_051: 07.0 (Monday morning 07:00 turn on)
P_052: 18.0 (Monday evening 18:00 turn off)
P_053: 07.0 (Tuesday morning 07:00 turn on)
P_054: 18.0 (Tuesday evening 18:00 turn off)
P_055: 07.0 (Wednesday morning 07:00 turn on)
P_056: 18.0 (Wednesday evening 18:00 turn off)
P_057: 07.0 (Tuesday morning 07:00 turn on)
P_058: 18.0 (Tuesday evening 18:00 turn off)
P_059: 07.0 (Friday morning 07:00 turn on)
P_060: 18.0 (Friday evening 18:00 turn off)
P_061: 07.0 (Saturday morning 07:00 turn on)
P_062: 13.3 (Saturday noon 13:30 turn off)
P_063: 24.0 (Sunday no turn on time, last operation mode continues)
P_064: 24.0 (Sunday no turn off time, last operation mode continues)
If the same time is used for turn on and turn off, then it will be considered as a turn-on time.
The unit has a battery backed-up precision real time clock circuit. The real time clock circuit will
continue its operation even in power failures. The real time clock is precisely trimmed using the program
parameter P_046. For more details check the programming section.