DKG-307 User Manual V-01.03
(14.02.2006)
- 19 -
Pgm Definition Unit Std Val Description
36 Horn Timer sec 10
This is the period during which the HORN relay
is active. If the period is set to 0, this will mean
that the period is unlimited.
37 Engine Heating Type - 0 This parameter defines the engine heating
method. The genset will not take the load
before engine heating is completed.
0: engine is heated during the period defined
by the Engine Heating Timer (P_029).
1: engine is heated until the coolant
temperature reaches the temperature defined
by Engine Heating Temperature (P_022) and
at least during the period defined by the
Engine Heating Timer (P_029).
38 Charge input alarm - 0
0: The charge input generates CHARGE
warning, and does not stop the engine.
1: The charge input generates CHARGE alarm,
and stops the engine.
39 Genset L-L Voltages - 0
0: Display genset Line to Neutral voltages,
1: Display genset Line to Line voltages.
40 Mains L-L Voltages - 0
0: Display mains Line to Neutral voltages,
1: Display mains Line to Line voltages.
41 Emergency Backup
Operation
- 0
0: In TEST mode, the load will not be
transferred to the genset even if the mains fail.
1: In TEST mode, the load will be transferred to
the genset if the mains fail.
42 Remote Start Operation - 0
0: Not REMOTE START mode, the engine
runs when the mains fail.
1: REMOTE START mode, the unit does not
monitor mains voltages, the engine runs when
a signal from the REMOTE START (22) comes.
43 Modem Connection - 0
0: No modem connection, the serial port is
connected to PC
1: Modem connected.
44 Maintenance Period
(Engine Hours)
hours 200
The SERVICE REQUEST led indicator will turn
on after this quantity of engine hours from the
last service. If the period is set to ‘0’ no
SERVICE REQUEST will be generated
depending on engine hours.
45 Maintenance Period
(Months)
month 6
The SERVICE REQUEST led indicator will turn
on after this amount of time from the last
service. If the period is set to ‘0’ no SERVICE
REQUEST will be indicated depending on time
46 Real Time Clock trimming - 0 This parameter is intended to trim precisely the
real time clock speed.
Values from 0 to 63 speed up the clock with
0.25sec/day steps.
Values from 127 to 64 slow down the clock with
0.25sec/day steps.
47 Not used
48 Not used
49 Not used
50 Not used
The parameters from P_051 to P_064 program the weekly operation schedule feature. For each
day of week, one turn_on time and one turn_off time are provided. Times are defined with 10 minute steps
and are shown in the 3 digit display as the hours and the first digit of the minutes. If no operation is needed
for a certain day of week, then the related time will be defined as 24.0; thus the last definition will continue
to be valid. For example if the turn_on and turn_off times for Sunday are given as 24.0 then the unit will not