Datakom DKG-307 Bedienungsanleitung Seite 28

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 29
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 27
DKG-307 User Manual V-01.03
(14.02.2006)
- 28 -
14. TECHNICAL SPECIFICATIONS
Alternator voltage: 0 to 300 V-AC (Ph-N)
Alternator frequency: 0-100 Hz.
Mains voltage: 0 to 300 V-AC (Ph-N)
Current inputs: from current transformers, .../5A. Max load 0.7VA per phase.
Digital inputs: input voltage 0 - 30 V-DC. Internally connected to battery positive via 4700 ohm resistor.
Analog inputs: Resistor input 0 to 5000 ohms connected to the battery negative. Sources 10 mA when closed
to battery negative.
Measurement category: CAT II
Air category: Pollution degree II
DC Supply range: 9.0 V-DC to 30.0 V-DC
Cranking dropouts: survives 0 V for 100ms
Typical current consumption: 100 mA-DC.
Maximum current consumption: 350 mA-DC (Relay outputs open)
Generator/mains contactor outputs: 16 A / 250 V.
DC relay outputs: 10A / 28 V.
Max. current for each terminal: 10A-RMS.
Charge alternator excitation current: 54 mA-DC @ 12 V-DC.
Communication port: RS-232. 2400 bauds, no parity, 1 stop bit.
Operating temperature range: -20°C to +70°C (-4 ºF to +158 ºF)
Storage temperature range: -40°C to +80°C (-40 ºF to +176 ºF)
Maximum humidity: 95%, non-condensing
IP protection: IP65 from front panel, IP30 from the rear
Dimensions: 155 x 115 x 48mm (WxHxD)
Mounting opening dimensions: 151 x 111mm minimum.
Mounting: Front panel mounted, retaining steel spring at the rear
Weight: 360 g (approx.)
Case material: High temperature, self extinguishing ABS (UL94-V0, 110 °C)