DKG-307 User Manual V-42 (24.05.2013)
- 33 -
PGM
Parameter Definition
Unit
Fact.Set
Description
P_000
Current Transformer
Ratio
A
500
This is the rated value of current transformers.
All transformers must have the same rating.
The secondary of the transformer will be 5 Amps.
P_001
Overcurrent Limit
A
0
If the current goes above this limit, during the
period defined in Overload Timeout then a
Overcurrent Load Dump alarm will be generated.
If this parameter is 0 then Overcurrent check is
disabled.
P_002
Excess Power Limit
KW
0
If the active power goes above this limit, during the
period defined in Overload Timeout then an
Excess Power Load Dump alarm will be
generated.
If this parameter is 0 then Excess Power check is
disabled.
P_003
Mains Voltage Low
Limit
V
170
If one of the mains phases goes under this limit, it
means that the mains are off and it starts the
transfer to the genset in AUTO mode.
P_004
Mains Voltage High
Limit
V
270
If one of the mains phases goes over this limit, it
means that the mains are off and it starts the
transfer to the genset in AUTO mode.
P_005
Mains Frequency Low
Limit
Hz
45
If the mains frequency goes under this limit, it
means that the mains are off and it starts the
transfer to the genset in AUTO mode.
P_006
Mains Frequency
High Limit
Hz
55
If the mains frequency goes above this limit, it
means that the mains are off and it starts the
transfer to the genset in AUTO mode.
P_007
Genset Low Voltage
Shutdown Limit
V
190
If one of the generator phase voltages goes under
this limit when feeding the load, this will generate a
GENSET LOW VOLTAGE shutdown alarm and
the engine will stop.
P_008
Genset Low Voltage
Warning Limit
V
200
If one of the generator phase voltages goes under
this limit when feeding the load, this will generate a
GENSET LOW VOLTAGE warning.
P_009
Genset High Voltage
Warning Limit
V
250
If one of the generator phase voltages goes above
this limit when feeding the load, this will generate a
GENSET HIGH VOLTAGE warning.
P_010
Genset High Voltage
Shutdown Limit
V
260
If one of the generator phase voltages goes over
this limit when feeding the load, this will generate a
GENSET HIGH VOLTAGE alarm and the engine
will stop.
P_011
Low Frequency
Shutdown
Hz
30
If the genset frequency goes under this limit, a
GENSET LOW SPEED alarm is generated and the
engine stops.
P_012
Low Frequency
Warning
Hz
35
If the genset frequency goes under this limit, a
GENSET LOW SPEED warning is generated.
P_013
High Frequency
Warning
Hz
54
If the genset frequency goes over this limit, a
GENSET HIGH SPEED warning is generated.
P_014
High Frequency
Shutdown
Hz
55
If the genset frequency goes over this limit, a
GENSET HIGH SPEED alarm is generated and the
engine stops.
P_015
Low Battery Voltage
Warning
V
9.0
If the battery voltage falls below this limit, this will
generate a LOW BATTERY warning.
P_016
High Battery Voltage
Warning
V
31.0
If the battery voltage goes over this limit, this will
generate a HIGH BATTERY warning.
P_017
High Battery Voltage
Shutdown
V
33.0
If the battery voltage goes over this limit, this will
generate a HIGH BATTERY shutdown alarm and
the engine will stop.